top of page
Search

How Often Should a Commercial HVAC System Be Serviced?

Writer: Van Bremen's Heat & Air
Van Bremen's Heat & Air
34 minutes ago
5 min read

A commercial HVAC system needs attention on several schedules at once: some checks monthly, some each season, and some once a year. ASHRAE Standard 180, an ANSI-approved standard co-sponsored by the Air Conditioning Contractors of America, sets minimum inspection and maintenance requirements meant to preserve a commercial building system's thermal comfort, energy efficiency and indoor air quality. The Minnesota Department of Administration's HVAC checklist for state buildings turns that idea into a calendar: filters, fans, supply diffusers and return grilles every month, cooling coils and drain pans during cooling season, outdoor air intakes every three months, and supply ductwork once a year.

 

A good maintenance plan also accounts for the rules that apply to the equipment. Federal refrigerant leak repair requirements under 40 CFR 82.157 apply only to appliances holding 50 or more pounds of ozone-depleting refrigerant, such as older R-22 systems, and not to equipment that uses only substitute refrigerants. Since January 1, 2025, new light commercial air conditioners and heat pumps generally must use refrigerants with a global warming potential below 700 under 40 CFR 84.54. This guide covers what ASHRAE 180 is, what to check and when, how heating equipment fits in, and when an energy audit makes sense for a small business in Somerset County.


Professional HVAC system assessment and diagnostic equipment in Somerset Pennsylvania home

What Is ASHRAE Standard 180?

 

ASHRAE Standard 180, titled Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems, establishes minimum inspection and maintenance requirements for new and existing commercial buildings. ASHRAE describes its purpose as preserving a system's ability to achieve acceptable thermal comfort, energy efficiency and indoor air quality.

 

The current edition is 180-2018. It is approved by the American National Standards Institute and co-sponsored by ACCA, the contractors' association. It gives building owners and service contractors a shared baseline, so a maintenance agreement can point to a recognized standard.

 

What Should Be Checked Every Month?

 

The Minnesota Department of Administration's annual checklist, written for each air handling unit in a building, lists four monthly checks:

 

  • Filters. Dirty filters restrict airflow.

  • Fans. Check that fans run as they should.

  • Supply diffusers. Make sure air is reaching occupied spaces.

  • Return grilles. Keep them open and clear.

 

The checklist has a box for each month from January to December, initialed when the task is done. The record shows what was checked and when.

 

For filter types and change intervals, the guide to how often HVAC air filters should be changed covers filter basics.

 

What Should Be Checked Each Season and Quarter?

 

The Minnesota checklist ties some tasks to the season or a quarterly cycle:

 

Task

When

Cooling coil

During cooling season

Drain pan

During cooling season

Outdoor air intakes

Every 3 months

Supply ductwork

Annually

 

Outdoor air intakes deserve attention in a Somerset County winter. NOAA's 1991 to 2020 climate normals show the Somerset station averaging 96.2 inches of snow a year, with at least an inch on the ground on about 70 days, so intakes near ground level or on a roof can collect snow and debris.

 

Ductwork gets its own annual look. The guide to how often air ducts should be professionally cleaned explains what a duct inspection covers.

 

How Does Heating Equipment Fit Into Commercial Maintenance?

 

Commercial buildings that heat with furnaces, boilers or oil burners also need annual heating service, and manufacturers spell out what it covers:

 

  • Gas furnaces. Carrier recommends annual professional maintenance that includes inspecting internal parts such as the flame sensor.

  • Boilers. Weil-McLain describes annual service that can include checking controls and safety devices, venting, combustion and system pressure.

  • Oil burners. Beckett says a qualified technician must service its burners every year, including the oil filter, nozzle, cad cell, pump pressure and vent.

 

Schedule heating service before the first cold snap, and cooling service in spring, so each system gets attention before its busy season. The guide to the typical cost of HVAC maintenance service covers budgeting.

 

What About Shops, Garages and Work Bays?

 

Some small businesses heat a shop or service bay with a unit heater rather than a central system. Modine lists auto repair bays, body shops and woodworking areas among the uses for its Hot Dawg HDS separated combustion heater, which pulls 100% of its combustion air from outdoors and comes in sizes from 30,000 to 125,000 Btu per hour.

 

Separated combustion matters in a space full of dust, fumes or sawdust, because the burner does not draw air from the room. CPSC has warned that unvented fuel-burning heaters pose the greatest threat of carbon monoxide poisoning, so a vented unit and working carbon monoxide alarms belong in any heated work area. Add unit heaters to the annual heating service list, and check that their vents and intakes stay clear of snow.

 

Do Federal Refrigerant Rules Apply to Your Building?

 

It depends on the equipment. Under 40 CFR 82.157, federal leak repair requirements apply only to appliances with a full charge of 50 or more pounds of class I or class II refrigerant, the ozone-depleting kind such as R-22. They do not apply to appliances that contain only substitute refrigerants.

 

For new equipment, the EPA's Technology Transitions rule limits new residential and light commercial air conditioners and heat pumps to refrigerants with a global warming potential below 700 for systems installed from January 1, 2025. Variable refrigerant flow systems followed on January 1, 2026. The EPA's May 2026 final rule allows systems whose specified components were all made or imported before January 1, 2025 to still be installed.

 

If your building still runs an older R-22 rooftop unit or split system, ask your contractor to check the refrigerant charge and record keeping that applies to it.

 

When Does a Commercial Energy Audit Make Sense?

 

ASHRAE Standard 211 sets the practice for commercial building energy audits at three levels, Level 1, Level 2 and Level 3, with each level more detailed than the last.

 

An audit makes sense when energy bills climb without a clear reason, before replacing major equipment, or when a building changes use. Bring the maintenance records from your checklist to the audit. The guide to how annual service affects system lifespan explains why regular care matters for equipment life.

 

FAQ

 

How often should commercial HVAC filters be checked?

 

Monthly, on the Minnesota Department of Administration checklist. Change them whenever they are dirty.

 

What is ASHRAE 180?

 

It is the ANSI-approved standard, co-sponsored by ACCA, that sets minimum inspection and maintenance requirements for commercial building HVAC systems.

 

Do I need to fix every refrigerant leak under federal law?

 

Federal leak repair rules in 40 CFR 82.157 apply to appliances with 50 or more pounds of ozone-depleting refrigerant. Leaks in smaller or substitute-refrigerant systems still waste money and should be repaired.

 

How often should outdoor air intakes be inspected?

 

Every three months on the Minnesota checklist, and after heavy snow if intakes sit low or on a roof.

 

Does a small business need the same maintenance as a large building?

 

The tasks scale with the equipment. A small shop with one rooftop unit still needs filter checks, coil and drain pan cleaning, and annual heating service.

 

Should heating and cooling be serviced at different times?

 

Yes. Service heating equipment in the fall and cooling equipment in spring, so each is ready before its busy season.

 

Van Bremen's Heat & Air Serves Commercial Heating Customers

 

Van Bremen's Heat & Air specializes in both residential and commercial furnace solutions, and its maintenance service covers heating and cooling equipment. The office is at 214 Stoystown Rd in Somerset, serving Somerset, Fayette, Cambria and Westmoreland Counties and Morgantown, WV. See the maintenance services page and heating services page.

 

Visit Van Bremen's Heat & Air or call (814) 483-1735 today. Contact us for more information.


Van Bremen's Heat & Air

 
 
 

Comments


bottom of page